If you own or manage a building in Rochester, your exterior and exit doors are covered by building, fire and accessibility rules at the same time. This page explains the hardware in plain terms and says where the rules come from. My Locksmith Rochester NY Inc. has served Rochester and Monroe County since 2010 as a mobile service; for an overview of what we do for businesses, start with our commercial locksmith page.

Which codes apply to your building

Rochester, like the rest of New York outside New York City, follows the New York State Uniform Fire Prevention and Building Code. The 2025 edition took effect on December 31, 2025, and is based on the 2024 International Building Code. Buildings permitted before that were designed to the 2020 edition, based on the 2018 IBC. The two editions number their door sections differently, so this page cites the 2024 IBC number first and gives the 2018 number in parentheses.

The 2010 ADA Standards for Accessible Design apply under federal law whatever the building code says. NFPA 101 is not the base code in New York; it matters mainly for hospitals and other federally regulated health facilities. Which edition applies to your building is a question for the City of Rochester Bureau of Buildings and Compliance or the Rochester Fire Department’s fire marshal. Verify with your local code official before you rely on any section cited here; this page is a guide to the hardware, not a code ruling.

Rochester’s building stock makes these rules a daily matter. Downtown and East End restaurants and bars are Group A spaces, where the 50-person threshold below comes up constantly. Older brick buildings along Monroe Avenue, in the South Wedge and in the Neighborhood of the Arts often have rated steel frames that were installed decades ago and still carry their labels.

Exit devices and panic bars

An exit device is the horizontal bar or touchpad that opens a door in one push. The code question is not whether you want one but whether you must have one.

Under the IBC path New York follows, doors serving a Group H (high hazard) occupancy, and doors serving Group A (assembly) or Group E (educational) rooms with a calculated occupant load of 50 or more, may not have any latch or lock other than panic hardware or fire exit hardware. The trigger is the calculated load of the space, not how many people usually use the door. See 2024 IBC section 1010.2.8 (2018 IBC section 1010.1.10). The 2024 edition also moved two special cases into their own subsections: refrigeration machinery rooms over 1,000 square feet (1010.2.8.1) and rooms with large electrical equipment (1010.2.8.2). Whether adjacent rooms combine toward the threshold is a matter of interpretation, so work from the calculated occupant load for your space, not from a head count.

  • Panic hardware and fire exit hardware differ. Panic hardware is listed to UL 305. Fire exit hardware is listed to both UL 305 and UL 10C and cannot be dogged, so the latch projects every time the door closes. The door label will say “Fire Door to be Equipped with Fire Exit Hardware.”
  • Mounting height is 34 to 48 inches above the floor (2024 IBC section 1010.2.3; 2018 IBC section 1010.1.9.2), and the bar must open the door in one motion with no key or special knowledge.
  • An alarmed exit device is not delayed egress. A local alarm that sounds on push does not restrict egress. Delayed egress holds the door for 15 seconds, requires sprinklers or smoke detection throughout the building, and is not permitted on doors serving Group H or most Group A spaces (2024 IBC section 1010.2.12; 2018 IBC section 1010.1.9.8). It is a permit item, not a hardware swap.

Worn exit devices often stop latching, which is both a security and a fire-door problem. Our commercial door repair service covers exit devices, closers and the doors and frames they mount to.

Electric strikes and buzzer entry

A buzzer entry system is an electric strike in the frame, a power supply, and a release button or intercom relay at the desk. The strike holds the latch until someone releases it, but the person inside can still turn the lever or push the bar to leave. Because it controls entry only, it is the lowest-code-risk way to add remote entry.

  • Fail-secure or fail-safe. Fail-secure stays locked when power drops and is the normal choice for a perimeter door. Fail-safe unlocks on power loss. Fire-rated strikes are listed fail-secure only, because a fire door must stay latched; if a fire door must unlock on power loss, use electrified trim or fire exit hardware instead.
  • Rated frames. Cutting a strike pocket into a fire-rated frame is a field modification under NFPA 80 and needs written approval from the frame manufacturer or listing lab, or the label is void. Get that approval on paper before anyone cuts.

We install keyless and electronic locks for commercial doors; see keyless door locks.

Door closers

A closer that slams, leaks oil or leaves the door open an inch is usually undersized, worn out or set wrong. Closers are graded under ANSI/BHMA A156.4 by tested cycles; Grade 1 is the heaviest duty and the usual choice for exterior, high-traffic and fire doors.

  • Opening force. Interior hinged doors must open with no more than 5 pounds of force, measured after the latch releases (ADA section 404.2.9). Fire and exterior doors have no ADA limit; the IBC caps other swinging doors at 30 pounds to set in motion and 15 pounds to swing open (section 1010.1.3 in both editions). Some jurisdictions add an exterior limit.
  • Closing speed. A door must take at least 5 seconds to close from 90 degrees to 12 degrees from the latch (ADA section 404.2.8.1). Many doors fail because someone tightened the sweep valve to make the door latch.

On a heavy or drafty door those two limits fight each other, and the fix is often a correctly sized closer rather than more turns of a screwdriver. On a fire door the closer must be listed, and hold-open arms are allowed only when released by smoke detection under NFPA 80. Propping a fire door is a deficiency.

Master key systems

A master key system lets one key open many doors while each tenant or employee key opens only its own. ANSI/BHMA A156.28 describes the levels: change keys only, change keys plus a master, a grand master above that, and a great grand master above that. Manufacturers advise against going past four levels, because every level adds master pins and raises the chance of keys that open doors they were never meant to.

Good systems start with a keying conference that decides who holds which level and who keeps the records. Key control is a policy, not a stamp: “Do Not Duplicate” on a standard key is unenforceable at a hardware store. Only a restricted or patented keyway, where keys are cut by the authorized dealer alone, gives you real control over copies. We work with Medeco, Mul-T-Lock, ASSA, Kaba and Schlage; see high security locks.

Plan for a lost top-level master, because it compromises every cylinder under it; interchangeable cores make that day cheaper. Read more on our master key system page.

ADA and fire-code hardware

The 2010 ADA Standards set the hardware rules you will be measured against, and the state code references ICC A117.1, which agrees on the numbers that matter:

  • Hardware must work with one hand, without tight grasping, pinching or twisting of the wrist, mounted 34 to 48 inches above the floor, with no more than 5 pounds of operating force (sections 404.2.7 and 309). Levers, push plates and panic bars pass. Knobs do not.
  • Clear width is 32 inches minimum at 90 degrees, with nothing projecting into it below 34 inches (section 404.2.3).

Fire-rated doors follow NFPA 80. Every swinging fire door must self-close and positively latch, and every piece of hardware on it must be listed for the assembly with the label legible. Dogged panic bars, fail-safe strikes, surface bolts, kick-down stops and wedges are all deficiencies. NFPA 80 section 5.2 requires an annual inspection with a written record, and the Fire Code of New York State section 705.2 requires opening protectives to be maintained to NFPA 80. Your insurer may ask to see that record as well.

ADA and the state code are enforced separately, so a door can pass one and be cited under the other. For lock functions that satisfy both, see commercial locks.

Rekey programs for property managers

New York State has no statute that requires a landlord to rekey between tenants. Rekeying at turnover is a liability and lease matter, not a code mandate. Confirm that with your attorney, along with whether the Multiple Dwelling Law or local property code adds requirements for your building.

A workable program has four parts: interchangeable cores for fast turnover, a building master with a change key per unit, a written key log, and a restricted keyway so tenants cannot copy keys. Our rekey service covers commercial and multi-unit properties as well as single doors.

On evictions, New York permits a lockout only after a court-ordered warrant executed by the sheriff or a marshal, not on a landlord’s request alone. A locksmith who changes a tenant’s lock without that warrant exposes the owner to a claim, so expect to be asked for the paperwork.

Multi-site and corporate accounts

Facility teams with several buildings save money by standardizing: one keyway or core family, one closer model, one exit device series across sites. Stock goes down and every technician knows the hardware.

We offer corporate accounts with billing for businesses that want one vendor for lockouts, repairs, rekeys and hardware across locations. Emergency response in the Rochester area is typically 20 to 30 minutes, depending on traffic and where the technician is coming from. For sites outside Monroe County, we will tell you what to expect when you call rather than promise the same window.

How a service visit works

You call (585) 360-0131 any hour, any day. Tell us the door type, what it does wrong, and whether it carries a fire label. We come to your address in Rochester or Monroe County; there is no walk-in storefront. Expect questions about the label, the frame and the closer before any hardware is recommended, because those answers decide what the code allows on that door.

Hardware we install carries a parts and labor warranty; ask for the current terms when you call. Our technicians are background checked, we are bonded and insured with a certificate of insurance available on request, BBB Accredited since 2018 with an A+ rating, and a member of ALOA, the Associated Locksmiths of America.

Frequently asked questions

Can I put an electric strike on a fire-rated door?

Yes, with three conditions. The strike must be listed for fire doors, which means it is fail-secure. The frame cut must be approved in writing by the frame manufacturer or the listing lab, because NFPA 80 treats it as a field modification. And the door must still self-close and latch every time. If the opening needs to unlock when power fails, an electric strike is the wrong product; use electrified lever trim or fire exit hardware with an electric latch retraction.

Why does my door closer slam?

Usually one of four things. The latch-speed valve is open too far, so the last few inches run unchecked. The closer is leaking oil, which means the seals have failed and hydraulic control is gone; a leaking closer is replaced, not adjusted. The closer is undersized for the door’s weight or for wind on an exterior opening. Or the backcheck was turned off and the door is bouncing off the stop. Adjust valves a quarter turn at a time, then confirm the door still takes at least 5 seconds to close from 90 degrees to 12 degrees.

Can my building owner require me to use a specific key system?

Usually, yes, through the lease. Most commercial leases require the tenant’s doors to stay on the building master system so the owner can enter for emergencies and maintenance, and they prohibit changing cylinders without consent. If you want to control copies of your own keys, ask the owner to put your suite on a restricted keyway within their system rather than installing a cylinder of your own. Read the lease before you call a locksmith.

How often must fire doors be inspected?

Once a year, under NFPA 80 section 5.2, with a written record kept for the fire marshal, and again after any work that touches the door, frame or hardware. The ADA and fire-code section above lists the deficiencies inspectors look for first.

Do I need a permit to replace an exit device or closer?

Replacing a device with the same type is generally treated as maintenance. Changing how the door works is different: adding delayed egress, an electrified lock, an access control system or anything that ties into the fire alarm is a permit question for the City of Rochester Bureau of Buildings and Compliance, and the fire marshal may want to see the release sequence. Ask before the hardware is ordered, not after it is installed.